(item no. 4991049)
Product overview: Fluke 710 mA Loop Valve Tester
Smart Control Valve Testing is now easier than ever
The Fluke 710 Valve Testing Loop Calibrator is designed to enable users to perform quick, easy tests on HART smart control valves. Featuring built-in test procedures and an intuitive user interface, the 710 allows users to quickly and easily perform valve tests, while the valve test quick-check results provide at-a-glance diagnostics help you make maintenance decisions faster than ever. The valve health quick-check results let you know whether your valve is in good, marginal or in bad operating condition so you can quickly decide whether additional maintenance is necessary.
Valve testing and HART communication in a precision loop calibrator
With the 710 Valve Testing Loop Calibrator’s built in HART communication function, users can source a 4-20 mA signal to cause the smart control valve to move, while simultaneously interpreting the valve’s HART feedback signal to determine whether the valve is moving to the expected position. In addition to positional information, the measured pressure delivered from the valve’s internal I/P (which moves the valve) can be determined through the HART communication protocol.
The 710 has built-in test procedures that automatically increase and change the mA signal while monitoring the HART position and pressure feedback from the control valve, giving you a better overall picture of valve health at the simple push of a button.
Pre-configured valve tests, at-a-glance answers
Valve test routines built into the 710 include:
- Manual testing; manually change the mA signal and view the HART position and pressure variable information
- Full range ramping of the mA signal from 4 to 20 to 4 mA while recording the 0-100-0% position, or the pressures applied that move the valve from 0-100-0%
- Stepping the mA signal on the input to the valve in steps and evaluating the valves response to the mA input changes
- Speed tests to determine how fast the valve can open or close
- Bump and partial stroke tests that help test valves over a portion of their range so they can be tested in a live process
ValveTrack™ Software enables further analysis and trending
Valve tests that are logged and recorded to memory in the 710 are available to upload to included ValveTrack™ analysis software.
ValveTrack™ software enables you to:
- Upload, print and plot logged valve tests taken in the field
- Compare previous uploaded tests to recent tests
- View valve test history by HART Tag ID
- Export valve test data to CSV for additional analysis in Microsoft Excel®
Saving time, getting answers
In addition, the 710 offers:
- Logging of HART data in the field. Once recorded by the 710 in the field, the ValveTrack™ software can upload the HART configuration of up to (20) HART devices in your plant and output data in either (.csv) or (.txt) format.
- Data logged mA loop measurements and HART data can be recorded from a particular transmitter for troubleshooting and loop tuning. The data log feature offers selectable capture with recording intervals of 1 to 60 seconds and a logging capacity of 4910 records or 99 individual sessions. Each record contains the mA measurement and all four process variables.
Product Highlights
- Valve test procedures that deliver Good, Marginal or Bad assessment of a control valve
- Generic HART communication
- Best-in-class mA accuracy at 0.01 % measurement or source value
- Compact rugged design
- Intuitive user interface with Quick-Set knob for fast setup, easy to use
- 24 V DC loop power with mA measure mode (-25 % to 125 %)
- Resolution of 1 μA on mA ranges and 1 mV on voltages ranges
- Built in selectable 250 Ω resistor for HART communications
- Simple two wire connection for all measurements
- Auto shutdown to conserve battery life
- Variable step and ramp time in seconds
HART communication
The Fluke 710 offers a built-in HART modem to communicate the following HART commands:
- Read sensor PV information
- Read PV output information
- Read and write PV unit type, tag ID name, descriptor, and message
- Read and write PV ranges (upper and lower)
- Enter/exit fixed current mode
- Set zero offset
- Trim DAC zero (mA output 4 mA)
- Trim DAC gain (mA output 20 mA)
HART Commands for Valves
The 710 includes these unique HART commands to support control valves:
- Autotrim of valve controller
In addition, the Fluke 710 offers:
- Logging of HART data in the field. Once recorded by the 710 in the field, the ValveTrack™ software can upload the HART configuration of up to 20 HART devices in your plant and output data in either .csv or .txt format
- Data-logged mA loop measurements and HART data can be recorded from a particular transmitter for troubleshooting and loop tuning. The data log feature offers selectable capture with recording intervals of 1 to 6 seconds and a logging capacity of 4910 records or 99 individual sessions. Each record contains the mA measurement and all four process variables.
Features
- Key valve testing functions include pre-configured valve signature test, speed test, step test, manual test, and bump/partial stroke test
- Key mA loop calibrator functions include mA source, mA simulate, mA read, mA read/loop power, and volts read
- ValveTrack™ Software enables upload to a PC for further in-depth analysis of valve measurements that are logged and recorded to memory
Specifications: Fluke 710 mA Loop Valve Tester
Detailed Specifications | |
Functions | mA source, mA simulate, mA read, mA read/loop power, and volts read. |
Ranges | mA (0 to 24 mA) and Volts (0 to 30 V DC) |
Resolution | 1 µA on mA ranges and 1 mV on voltage range |
Accuracy | 0.01% ± 2 counts, all ranges (@ 23 °C ± 5 °C [73.4 °F ± 41 °F]) |
Operating temperature range | -10°C to 55°C (14°F to 131°F) |
Humidity range | 10 to 95% non-condensing |
Stability | 20 ppm of F.S. /°C from -10°C to 18°C and 28°C to 55°C |
Display | 128 x 64 pixels, LCD Graphic w/backlight, .34 high digits |
Power | 6 AAA alkaline |
Battery life | 40 hours continuous use (measure mode using) |
Loop compliance voltage | 24 V DC @ 20mA |
Over-voltage protection | 240 V AC |
Overload current protection | 28 mA DC |
EMC | EN61326 Annex A (Portable Instruments) |
Dimensions (L x W x D) | 15 x 9 x 3 cm (6 x 3.6 x 1.3 in) |
Weight | 0.3 kg (9.5 oz) |
Included accessories | Traceable calibration certificate with data, batteries, test leads, USB upload cable and safety |
Warranty | Three year |
Includes:
- Stackable test lead set
- Extended tooth alligator clip set
- TP220 test probes
- AC280 SureGrip™ hook clips
- Lemo to USB upload/download cable
- ValveTrack™ software (free download)
- Softcase
- Six AAA batteries (installed)
- 709/709H/710 Product manual CD-ROM
- 709/709H/710 Quick reference guide
- 709/709H/710 Safety information
Manuals
- 709/709H/710 | Users manual
- 709/709H/710 | Statement of memory volatility
- 709/709H/710 | Safety sheet
- 709/709H/710 | Quick reference guide
- 709/709H/710 | Calibration manual
Data Sheets
Shipping | This Item Ships from Fremantle, Perth, Western Australia |
Please allow 2 - 10 days for your order to arrive.
Although Most Stocked Products will generally Ship Overnight. We source products from all over the world to bring you epic offers and the lowest prices. This means sometimes you have to wait a little longer to get your order but it's always worth it!
Returns are easy.
simply contact us for a returns number and send your item to our returns centre for fast processing. We'll get you a replacement or refund in a snap!
Description
(item no. 4991049)
Product overview: Fluke 710 mA Loop Valve Tester
Smart Control Valve Testing is now easier than ever
The Fluke 710 Valve Testing Loop Calibrator is designed to enable users to perform quick, easy tests on HART smart control valves. Featuring built-in test procedures and an intuitive user interface, the 710 allows users to quickly and easily perform valve tests, while the valve test quick-check results provide at-a-glance diagnostics help you make maintenance decisions faster than ever. The valve health quick-check results let you know whether your valve is in good, marginal or in bad operating condition so you can quickly decide whether additional maintenance is necessary.
Valve testing and HART communication in a precision loop calibrator
With the 710 Valve Testing Loop Calibrator’s built in HART communication function, users can source a 4-20 mA signal to cause the smart control valve to move, while simultaneously interpreting the valve’s HART feedback signal to determine whether the valve is moving to the expected position. In addition to positional information, the measured pressure delivered from the valve’s internal I/P (which moves the valve) can be determined through the HART communication protocol.
The 710 has built-in test procedures that automatically increase and change the mA signal while monitoring the HART position and pressure feedback from the control valve, giving you a better overall picture of valve health at the simple push of a button.
Pre-configured valve tests, at-a-glance answers
Valve test routines built into the 710 include:
- Manual testing; manually change the mA signal and view the HART position and pressure variable information
- Full range ramping of the mA signal from 4 to 20 to 4 mA while recording the 0-100-0% position, or the pressures applied that move the valve from 0-100-0%
- Stepping the mA signal on the input to the valve in steps and evaluating the valves response to the mA input changes
- Speed tests to determine how fast the valve can open or close
- Bump and partial stroke tests that help test valves over a portion of their range so they can be tested in a live process
ValveTrack™ Software enables further analysis and trending
Valve tests that are logged and recorded to memory in the 710 are available to upload to included ValveTrack™ analysis software.
ValveTrack™ software enables you to:
- Upload, print and plot logged valve tests taken in the field
- Compare previous uploaded tests to recent tests
- View valve test history by HART Tag ID
- Export valve test data to CSV for additional analysis in Microsoft Excel®
Saving time, getting answers
In addition, the 710 offers:
- Logging of HART data in the field. Once recorded by the 710 in the field, the ValveTrack™ software can upload the HART configuration of up to (20) HART devices in your plant and output data in either (.csv) or (.txt) format.
- Data logged mA loop measurements and HART data can be recorded from a particular transmitter for troubleshooting and loop tuning. The data log feature offers selectable capture with recording intervals of 1 to 60 seconds and a logging capacity of 4910 records or 99 individual sessions. Each record contains the mA measurement and all four process variables.
Product Highlights
- Valve test procedures that deliver Good, Marginal or Bad assessment of a control valve
- Generic HART communication
- Best-in-class mA accuracy at 0.01 % measurement or source value
- Compact rugged design
- Intuitive user interface with Quick-Set knob for fast setup, easy to use
- 24 V DC loop power with mA measure mode (-25 % to 125 %)
- Resolution of 1 μA on mA ranges and 1 mV on voltages ranges
- Built in selectable 250 Ω resistor for HART communications
- Simple two wire connection for all measurements
- Auto shutdown to conserve battery life
- Variable step and ramp time in seconds
HART communication
The Fluke 710 offers a built-in HART modem to communicate the following HART commands:
- Read sensor PV information
- Read PV output information
- Read and write PV unit type, tag ID name, descriptor, and message
- Read and write PV ranges (upper and lower)
- Enter/exit fixed current mode
- Set zero offset
- Trim DAC zero (mA output 4 mA)
- Trim DAC gain (mA output 20 mA)
HART Commands for Valves
The 710 includes these unique HART commands to support control valves:
- Autotrim of valve controller
In addition, the Fluke 710 offers:
- Logging of HART data in the field. Once recorded by the 710 in the field, the ValveTrack™ software can upload the HART configuration of up to 20 HART devices in your plant and output data in either .csv or .txt format
- Data-logged mA loop measurements and HART data can be recorded from a particular transmitter for troubleshooting and loop tuning. The data log feature offers selectable capture with recording intervals of 1 to 6 seconds and a logging capacity of 4910 records or 99 individual sessions. Each record contains the mA measurement and all four process variables.
Features
- Key valve testing functions include pre-configured valve signature test, speed test, step test, manual test, and bump/partial stroke test
- Key mA loop calibrator functions include mA source, mA simulate, mA read, mA read/loop power, and volts read
- ValveTrack™ Software enables upload to a PC for further in-depth analysis of valve measurements that are logged and recorded to memory
Specifications: Fluke 710 mA Loop Valve Tester
Detailed Specifications | |
Functions | mA source, mA simulate, mA read, mA read/loop power, and volts read. |
Ranges | mA (0 to 24 mA) and Volts (0 to 30 V DC) |
Resolution | 1 µA on mA ranges and 1 mV on voltage range |
Accuracy | 0.01% ± 2 counts, all ranges (@ 23 °C ± 5 °C [73.4 °F ± 41 °F]) |
Operating temperature range | -10°C to 55°C (14°F to 131°F) |
Humidity range | 10 to 95% non-condensing |
Stability | 20 ppm of F.S. /°C from -10°C to 18°C and 28°C to 55°C |
Display | 128 x 64 pixels, LCD Graphic w/backlight, .34 high digits |
Power | 6 AAA alkaline |
Battery life | 40 hours continuous use (measure mode using) |
Loop compliance voltage | 24 V DC @ 20mA |
Over-voltage protection | 240 V AC |
Overload current protection | 28 mA DC |
EMC | EN61326 Annex A (Portable Instruments) |
Dimensions (L x W x D) | 15 x 9 x 3 cm (6 x 3.6 x 1.3 in) |
Weight | 0.3 kg (9.5 oz) |
Included accessories | Traceable calibration certificate with data, batteries, test leads, USB upload cable and safety |
Warranty | Three year |
Includes:
- Stackable test lead set
- Extended tooth alligator clip set
- TP220 test probes
- AC280 SureGrip™ hook clips
- Lemo to USB upload/download cable
- ValveTrack™ software (free download)
- Softcase
- Six AAA batteries (installed)
- 709/709H/710 Product manual CD-ROM
- 709/709H/710 Quick reference guide
- 709/709H/710 Safety information
Manuals
- 709/709H/710 | Users manual
- 709/709H/710 | Statement of memory volatility
- 709/709H/710 | Safety sheet
- 709/709H/710 | Quick reference guide
- 709/709H/710 | Calibration manual
Data Sheets
Shipping
Shipping | This item ships to |
Delivery & Returns
Please allow 2 - 10 days for your order to arrive.
Although Most Stocked Products will generally Ship Overnight. We source products from all over the world to bring you epic offers and the lowest prices. This means sometimes you have to wait a little longer to get your order but it's always worth it!
Returns are easy.
simply contact us for a returns number and send your item to our returns centre for fast processing. We'll get you a replacement or refund in a snap!
Reviews
6 Great reasons to buy from us:
-
30 Days Return
If your product is faulty or damaged under manufacture warranty, simply send it back to us and we'll cheerfully replace it or fix the problem for you. -
Returns are Easy
Simply contact us for a returns number and send your item to our returns centre for fast processing. We'll get you a replacement or refund in a snap! -
Best Price Guarantee
In the unlikely event that you find your item cheaper at another online store, just let us know and we'll beat the competitor's pricing hands-down. -
We guarantee your satisfaction
We insist that you love everything you buy from us. If you're unhappy for any reason whatsoever, just let us know and we'll bend over backwards to make things right again. -
100% Safe & Secure
Ordering from Laserman Technologies is 100% safe and secure so you can rest easy. Your personal details are never shared, sold or rented to anyone either. -
Best Laser Warranties in the Business
Laserman the Best Laser Level, Pipe Laser and Laser Measuring Warranties in the Business - Now thats unbeatable value !!.